Single Acting Actuator
20 to 60 psi (140 to 400 kPa)
Double Acting Actuator
30 to 100 psi (200 to 700 kPa)
Vibration Limit
4 mm at 5 to 15 Hz; 2G at 15 to 2000 Hz
Manual Operation
Available using Auto/Manual (A/M) transfer switch
Zero Adjustment Range
-15 to 85% of span
Span Adjustment Range
Within 300% of span
Ambient Temperature Effect
0.08% of Span/°C
Position Effect
0.3% of Span/90 deg
Vibration Effect
2% of Span at 2G (15 to 2000 Hz)